Studying the Effect of Adding the Concrete Reinforcement Grid Rods to the Grounding System of the Mosul Secondary University Distribution Station | ||
Al-Rafidain Engineering Journal (AREJ) | ||
Article 16, Volume 26, Issue 2, October 2021, Pages 179-186 PDF (2.23 M) | ||
Document Type: Research Paper | ||
DOI: 10.33899/rengj.2021.130845.1122 | ||
Authors | ||
Saleh k. Ahmad Algehiche* ; Riyadh Zaki Sabry | ||
Electrical Engineering Department, Collage of Engineering, University of Mosul | ||
Abstract | ||
In this research, a study was conducted to re-evaluate the safety levels of the grounding system for the Mosul Secondary University distribution station, by taking the effect of the conductors of the foundation arming grid on the electrical potential distribution resulting from faults to the grounding system implemented by the Lebanese company (MATELEC s.a.l). A fault current of (20kA) was adopted. The CYMGRD program was used to re-design the grounding system implemented by the company in two stages, first without taking the effect of the arming grid of the foundations, and then the grounding system was redesigned by adding the arming grid of the foundations implemented inside the concrete and linking it with the basic grounding system that was formed of conductors and grounding rods, and the results showed the significant effect of the foundation arming grid in reducing the levels of touch voltage (Em) by 33%. | ||
Keywords | ||
Foundation Reinforcing Grid; Potential Distribution; Grounding System; Touch Voltage (Em) | ||